Printable motor full-load current chart

Full-load amps for three-phase motors at 208 to 575 V with the copper size for each, and typical IEC amps at 400 V. One sheet, fits A4 and US Letter.

Download Excel (.xlsx) Print, or choose “Save as PDF” in the print dialog. The Excel file has every table as its own sortable tab.

Motor full-load current & cable

NEC 430.250 three-phase FLA · copper size at 125% · IEC 400 V typical amps

tililt.com

NEC 430.250 — three-phase full-load amps, and copper AWG

HP208 V230 V460 V575 VCu 230 VCu 460 V
1/22.42.21.10.91414
3/43.53.21.61.31414
14.64.22.11.71414
1-1/26.6632.41414
27.56.83.42.71414
310.69.64.83.91414
516.715.27.66.11414
7-1/224.2221191014
1030.82814111014
1546.2422117610
2059.4542722410
2574.868342748
308880403238
40114104524116
5014313065522/04
6016915477623/03
752111929677250k1
10027324812499350k2/0
1253433121561252×3/03/0
1503963601801442×4/04/0
2005284802401922×350k350k
250——302242—500k
300——361289—2×4/0
350——414336—2×300k
400——477382—2×350k
500——590472—2×500k

Cu = smallest 75 °C copper for the branch circuit at 125% of the table current (NEC 430.22). 250k = 250 kcmil; 2× = two conductors in parallel per phase.

IEC — typical amps, 4-pole IE3, 50 Hz

kWHP400 V230 V
0.370.511.7
0.550.71.42.4
0.751.01.72.9
1.11.52.44.2
1.52.03.35.7
2.23.04.68.0
34.06.210.7
45.48.114.0
5.57.41119
7.51014.826
11152136
152028.549
18.5253561
22304171
30405595
375067116
456081140
557499171
75101135234
90121160277
110148195338
132177230398
160215280485
200268350606
250335430745
315422540935

230 V is the same motor connected in delta. Use these to choose a starter before the motor is bought; after that, the nameplate current rules.

NEC table currents are for sizing conductors, fuses and breakers (430.6); set the overload relay from the nameplate. Cable sizes ignore voltage drop, grouping and ambient — check long runs with the voltage drop calculator and your local code.

Get the next chart before it's on the site

The Shop Sheet, once a month: one new printable chart, and one standards gotcha that catches people out — the kind of wrong number a forum thread or an AI answer gives with total confidence. No sales emails.

More printable charts

Tap Drill ChartEvery common metric, UNC and UNF thread with its tap drill and clearance hole. The one for the wall above the drill press.Drill Size ChartAll 163 number, letter and fractional drills in one ascending run, with decimal inch, millimetres and the tap each one drills for.Bolt Torque ChartTightening torque for metric property classes and SAE grades, with the multiplier for oiled and anti-seize threads.Spanner & Allen Key ChartFor each bolt: the spanner or socket, the Allen key for its cap screw, the tap drill and the clearance hole.Wire Size ChartAWG ampacity at 60, 75 and 90 °C, and the copper size for any load and run length with voltage drop taken into account.Wire Ampacity Derating ChartHow far to derate copper for hot rooms and full conduits: temperature factors, conductor-count factors and the derated amps for every size from 14 AWG to 500 kcmil.Bearing Size ChartEvery common deep-groove ball bearing from 604 to 6320 by bore code and series, with what 2RS, ZZ and C3 mean.IEC Motor Frame ChartEvery IEC frame from 63 to 355: shaft height, foot hole spacing, shaft size and the kW normally built on it, plus B3/B5/B14.NEMA Motor Frame ChartNEMA T frames from 56 to 449T with shaft height, foot holes, shaft size and typical HP — and what C, TS and JM mean.Motor Efficiency Class ChartMinimum efficiency for IE1 to IE4 at every standard rating, and which class the EU lets you buy now.IE3/IE4 Motor Compliance Chart (EU 2026)Which IE class a new motor must be in the EU, whether an old IE1 or IE2 motor may keep running or be rewound, and what an upgrade saves — with a checker for your nameplate.