How far to derate copper for hot rooms and full conduits: temperature factors, conductor-count factors and the derated amps for every size from 14 AWG to 500 kcmil. One sheet, fits A4 and US Letter.
Download Excel (.xlsx)Print, or choose “Save as PDF” in the print
dialog. The Excel file has every table as its own sortable tab.
AdYour first print or download also opens an offer from our ad partner in a new tab; your file still comes here.Offers from our ad partner
Wire ampacity derating
Ambient correction · more than 3 conductors · derated copper by AWG
tililt.com
Ambient temperature correction — factor by insulation rating
°C
°F
60 °C
75 °C
90 °C
≤ 10
≤ 50
1.29
1.20
1.15
11–15
52–59
1.22
1.15
1.12
16–20
61–68
1.15
1.11
1.08
21–25
70–77
1.08
1.05
1.04
26–30
79–86
1.00
1.00
1.00
31–35
88–95
0.91
0.94
0.96
36–40
97–104
0.82
0.88
0.91
41–45
106–113
0.71
0.82
0.87
46–50
115–122
0.58
0.75
0.82
51–55
124–131
0.41
0.67
0.76
56–60
133–140
—
0.58
0.71
61–65
142–149
—
0.47
0.65
66–70
151–158
—
0.33
0.58
71–75
160–167
—
—
0.50
76–80
169–176
—
—
0.41
81–85
178–185
—
—
0.29
86–90
187–194
—
—
—
Adjustment for more than three current-carrying conductors
Conductors
Multiply by
4–6
80%
7–9
70%
10–20
50%
21–30
45%
31–40
40%
41 and up
35%
Count every current-carrying conductor in the raceway or
cable. The neutral of a balanced 3-phase wye circuit usually does not
count; the equipment ground never does.
Derated copper ampacity, A — 90 °C wire on 75 °C terminals, 30 °C ambient
AWG
1–3
4–6
7–9
10–20
4–6 at 40 °C
14
20
20
17
12
18
12
25
24
21
15
21
10
35
32
28
20
29
8
50
44
38
27
40
6
65
60
52
37
54
4
85
76
66
47
69
3
100
92
80
57
83
2
115
104
91
65
94
1
130
116
101
72
105
1/0
150
136
119
85
123
2/0
175
156
136
97
141
3/0
200
180
157
112
163
4/0
230
208
182
130
189
250k
255
232
203
145
211
300k
285
256
224
160
232
350k
310
280
245
175
254
400k
335
304
266
190
276
500k
380
344
301
215
313
Start from the 90 °C value, multiply by both factors,
then use the smaller of that and the 75 °C value. Example: six 10 AWG at
40 °C = 40 × 0.80 × 0.91 = 29 A. Last column
= 4–6 conductors in 40 °C air (× 0.80 × 0.91).