What size wire do I need for 70 amps at 250 feet?

Answer 2 AWG

A 70 amp circuit running 250 feet needs 2 AWG copper. It is sized by voltage drop, and lands at 2.8% voltage drop.

How it is worked out

  1. Ampacity — does it get too hot?4 AWG carries 70 A at 75 °C
  2. Voltage drop — does enough arrive?2 AWG keeps 250 ft inside 3%
  3. The larger of the two wins2 AWG

drop = 2 × I × R × L single phase, √3 × I × R × L three phase

Worth knowing

Voltage drop at this size
6.79 V — 2.8% of 240 V
Derated ampacity
115 A
Nearest metric size
35 mm²
Heat lost in the cable
475.3 W
Which one governed, and why
On a short run ampacity decides and the answer is whatever the breaker implies. Past twenty or thirty metres voltage drop takes over and grows without limit — here it is voltage drop.
Using aluminium instead
Roughly two sizes up for the same performance, and it has its own small-conductor limits: 12 AWG aluminium is capped at 15 A, not the 20 A a copper 12 gets.
What this does not cover
Conduit fill, ambient temperature above 30 °C, more than three current-carrying conductors, and your local code — all of which can push the answer up a size.