What size wire do I need for 15 amps at 75 feet?

Answer 14 AWG

A 15 amp circuit running 75 feet needs 14 AWG copper. It is sized by both, equally, and lands at 2.9% voltage drop.

How it is worked out

  1. Ampacity — does it get too hot?14 AWG carries 15 A at 75 °C
  2. Voltage drop — does enough arrive?14 AWG keeps 75 ft inside 3%
  3. The larger of the two wins14 AWG

drop = 2 × I × R × L single phase, √3 × I × R × L three phase

Worth knowing

Voltage drop at this size
7.07 V — 2.9% of 240 V
Derated ampacity
15 A
Nearest metric size
2.5 mm²
Heat lost in the cable
106 W
Which one governed, and why
On a short run ampacity decides and the answer is whatever the breaker implies. Past twenty or thirty metres voltage drop takes over and grows without limit — here it is both, equally.
Using aluminium instead
Roughly two sizes up for the same performance, and it has its own small-conductor limits: 12 AWG aluminium is capped at 15 A, not the 20 A a copper 12 gets.
What this does not cover
Conduit fill, ambient temperature above 30 °C, more than three current-carrying conductors, and your local code — all of which can push the answer up a size.

The same load at other distances

Other loads at this distance

Do it with your own numbers

This page answers one specific question. The Wire Size Calculator takes any values you like and answers as you type — in your browser, so nothing you enter is sent anywhere.